Backflow assembly test · 9475 Ridgeview Ct
ApprovedFiled Jun 15, 2024 by Hayden Ramirez, Patriot Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 15, 2024
- Assembly type
- RP
- Serial number
- A986125
- Size
- 3/4
- Test gauge serial
- G-1607
- Gauge calibration date
- Apr 15, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-28-01358
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.