Backflow assembly test: 1869 Hickory Ct
ApprovedFiled Feb 21, 2026 by Jamie Marsh, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Feb 21, 2026
- Assembly type
- PVB
- Serial number
- B593093
- Size
- 3/4
- Test gauge serial
- G-5254
- Gauge calibration date
- May 29, 2025
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jamie Marsh, current on the service date
- All required fields present
- Address matches parcel 077-16-01222
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.