Backflow assembly test · 5968 Ridgeview Ln
ApprovedFiled Jun 8, 2025 by Hayden Benton, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 8, 2025
- Assembly type
- RP
- Serial number
- A932891
- Size
- 3/4
- Test gauge serial
- G-9516
- Gauge calibration date
- Nov 25, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-47-01002
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.