← Backflow review queue

Backflow assembly test · 6873 Turkey Hill Ln

Approved

Filed Aug 26, 2025 by Morgan Calloway, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Aug 26, 2025
Assembly type
DC
Serial number
B478439
Size
1
Test gauge serial
G-1837
Gauge calibration date
Feb 25, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-66-01291
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.