← Backflow review queue
Backflow assembly test · 3742 Quarry Trl
ApprovedFiled Jun 6, 2025 by Logan Whitcomb, Lakeside Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 6, 2025
- Assembly type
- DC
- Serial number
- A992605
- Size
- 3/4
- Test gauge serial
- G-7224
- Gauge calibration date
- Feb 28, 2025
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-12-01001
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3742 Quarry Trl
Owner: Avery Ellery
Parcel 077-12-01001