Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2030 Meadow Lark Trl

Approved

Filed Oct 25, 2024 by Casey Nguyen, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Oct 25, 2024
Assembly type
RP
Serial number
B560060
Size
3/4
Test gauge serial
G-6381
Gauge calibration date
Apr 14, 2024
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-88-01043
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2030 Meadow Lark Trl
Owner: Avery Harlow
Parcel 081-88-01043