Backflow assembly test · 7444 Meadow Lark Trl

Approved

Filed Apr 28, 2025 by Logan Lindqvist, Ridge Backflow Testing · filed from phone

Report

Date of service
Apr 28, 2025
Assembly type
RP
Serial number
W958655
Size
1
Test gauge serial
G-7046
Gauge calibration date
Aug 8, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-66-01072
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.