Backflow assembly test · 790 Mill Creek Ct
ApprovedFiled Feb 25, 2026 by Logan Lindqvist, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Feb 25, 2026
- Assembly type
- RP
- Serial number
- A508898
- Size
- 1
- Test gauge serial
- G-3986
- Gauge calibration date
- Sep 24, 2025
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-34-01117
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
790 Mill Creek Ct
Owner: Hayden Stroud
Parcel 081-34-01117