Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5989 Stone Gate Trl

Approved

Filed Jul 15, 2025 by Taylor Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Jul 15, 2025
Assembly type
PVB
Serial number
A555868
Size
1
Test gauge serial
G-3581
Gauge calibration date
Nov 13, 2024
Check valve 1
5.7 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-81-01028
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5989 Stone Gate Trl
Owner: Rowan Vance
Parcel 081-81-01028