← Backflow review queue
Backflow assembly test · 9751 Laurel Ln
ApprovedFiled Oct 1, 2025 by Logan Lindqvist, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Oct 1, 2025
- Assembly type
- DC
- Serial number
- B714933
- Size
- 3/4
- Test gauge serial
- G-8489
- Gauge calibration date
- Jul 10, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 081-39-01284
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
9751 Laurel Ln
Owner: Reese Okafor
Parcel 081-39-01284