Moffat County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2156 Orchard Ct

Approved

Filed Sep 23, 2026 by Blake Ashby, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Sep 23, 2026
Assembly type
RP
Serial number
W893434
Size
3/4
Test gauge serial
G-6024
Gauge calibration date
Jul 6, 2026
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 081-23-01138
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2156 Orchard Ct
Owner: Jamie Ashby
Parcel 081-23-01138