Ouray County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Taqueria

Approved

Filed Jul 11, 2026 by Jamie Hollins, Clearwater Backflow Testing · filed from phone

Report

Date of service
Jul 11, 2026
Assembly type
RP
Serial number
Z518830
Size
1 1/2
Test gauge serial
G-4574
Gauge calibration date
May 22, 2026
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-80-01286
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2376 Stone Gate Way
Owner: Ellery Holdings LLC
Parcel 091-80-01286