Backflow assembly test · 6436 Mill Creek Ln
ApprovedFiled Nov 13, 2025 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Nov 13, 2025
- Assembly type
- RP
- Serial number
- B662144
- Size
- 3/4
- Test gauge serial
- G-8475
- Gauge calibration date
- Feb 23, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-35-01110
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6436 Mill Creek Ln
Owner: Alex Wexler
Parcel 091-35-01110