Backflow assembly test · 2692 Pine Knoll Rd
ApprovedFiled Apr 10, 2026 by Cameron Benton, Lakeside Backflow Testing · filed from phone
Report
- Date of service
- Apr 10, 2026
- Assembly type
- PVB
- Serial number
- Z679045
- Size
- 3/4
- Test gauge serial
- G-1093
- Gauge calibration date
- Jan 21, 2026
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-20-01193
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.