Backflow assembly test · 4304 Hickory Trl

Approved

Filed Sep 1, 2026 by Jamie Hollins, Clearwater Backflow Testing · filed from phone

Report

Date of service
Sep 1, 2026
Assembly type
DC
Serial number
W210693
Size
1
Test gauge serial
G-7700
Gauge calibration date
May 20, 2026
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-51-01012
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.