Backflow assembly test · Hilltop Apartments

Approved

Filed Oct 11, 2026 by Sam Calloway, Lakeside Backflow Testing · filed from phone

Report

Date of service
Oct 11, 2026
Assembly type
RP
Serial number
B406565
Size
4
Test gauge serial
G-1245
Gauge calibration date
Feb 5, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-39-01191
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2407 Old Church Rd
Owner: Nguyen Holdings LLC
Parcel 091-39-01191