← Backflow review queue

Backflow assembly test · 4380 Pine Knoll Trl

Approved

Filed Nov 3, 2026 by Jamie Hollins, Clearwater Backflow Testing · filed from phone

Report

Date of service
Nov 3, 2026
Assembly type
DC
Serial number
Z721105
Size
3/4
Test gauge serial
G-9441
Gauge calibration date
Jul 15, 2025
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 091-26-01310
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.