Backflow assembly test · 8850 Turkey Hill Way
ApprovedFiled May 18, 2026 by Jamie Hollins, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- May 18, 2026
- Assembly type
- DC
- Serial number
- W321421
- Size
- 1
- Test gauge serial
- G-5311
- Gauge calibration date
- Feb 22, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-62-01025
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.