← Backflow review queue
Backflow assembly test · 9585 Old Church Ln
ApprovedFiled Aug 4, 2024 by Jamie Hollins, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Aug 4, 2024
- Assembly type
- DC
- Serial number
- K907979
- Size
- 3/4
- Test gauge serial
- G-2975
- Gauge calibration date
- Nov 13, 2023
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 091-95-01127
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9585 Old Church Ln
Owner: Drew Hollins
Parcel 091-95-01127