Backflow assembly test · Maple Leaf Bakery
ApprovedFiled Feb 12, 2025 by Alex Wexler, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 12, 2025
- Assembly type
- DC
- Serial number
- W685519
- Size
- 1 1/2
- Test gauge serial
- G-6618
- Gauge calibration date
- Oct 31, 2024
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-29-01000
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8327 Mill Creek Rd
Owner: Vance Holdings LLC
Parcel 097-29-01000