← Backflow review queue
Backflow assembly test · Maple Leaf Market
ApprovedFiled Feb 12, 2026 by Alex Wexler, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 12, 2026
- Assembly type
- RP
- Serial number
- K648310
- Size
- 1
- Test gauge serial
- G-1685
- Gauge calibration date
- Apr 4, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-98-01085
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4939 Orchard Ln
Owner: Wexler Holdings LLC
Parcel 097-98-01085