Backflow assembly test · 866 Stone Gate Rd
ApprovedFiled Jul 25, 2026 by Reese Nguyen, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 25, 2026
- Assembly type
- RP
- Serial number
- Z737077
- Size
- 3/4
- Test gauge serial
- G-6863
- Gauge calibration date
- Mar 5, 2026
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-60-01062
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.