← Backflow review queue
Backflow assembly test · Station Pizza
Needs reviewFiled Nov 24, 2026 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 24, 2026
- Assembly type
- RP
- Serial number
- W276438
- Size
- 1
- Test gauge serial
- G-2768
- Gauge calibration date
- Mar 10, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-25-01320
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6138 Laurel Rd
Owner: Benton Holdings LLC
Parcel 107-25-01320