Backflow assembly test · 2989 Quarry Ct
ApprovedFiled Jul 27, 2026 by Reese Whitcomb, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 27, 2026
- Assembly type
- RP
- Serial number
- Z771213
- Size
- 1
- Test gauge serial
- G-2155
- Gauge calibration date
- Oct 21, 2025
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-90-01313
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.