← Backflow review queue
Backflow assembly test · 2209 Orchard Rd
ApprovedFiled Oct 20, 2024 by Taylor Vance, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 20, 2024
- Assembly type
- RP
- Serial number
- K712305
- Size
- 3/4
- Test gauge serial
- G-7507
- Gauge calibration date
- Aug 10, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-79-01077
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2209 Orchard Rd
Owner: Taylor Benton
Parcel 107-79-01077