Backflow assembly test · 1241 Quarry Dr

Approved

Filed Feb 13, 2024 by Reese Whitcomb, Heritage Backflow Testing · filed from phone

Report

Date of service
Feb 13, 2024
Assembly type
PVB
Serial number
K653239
Size
3/4
Test gauge serial
G-4555
Gauge calibration date
Sep 22, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-28-01163
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1241 Quarry Dr
Owner: Logan Fairley
Parcel 107-28-01163