Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1074 Ridgeview Ln

Approved

Filed Mar 20, 2025 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Mar 20, 2025
Assembly type
RP
Serial number
Z945258
Size
1
Test gauge serial
G-9379
Gauge calibration date
Feb 2, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-87-01341
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1074 Ridgeview Ln
Owner: Jordan Calloway
Parcel 107-87-01341