Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Self Storage

Approved

Filed Jul 30, 2026 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Jul 30, 2026
Assembly type
RP
Serial number
A601269
Size
1 1/2
Test gauge serial
G-9992
Gauge calibration date
Nov 10, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-46-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8833 Spring Branch Rd
Owner: Hollins Holdings LLC
Parcel 107-46-01296