Backflow assembly test · 4321 Quarry Trl
ApprovedFiled Feb 26, 2025 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 26, 2025
- Assembly type
- PVB
- Serial number
- K626947
- Size
- 3/4
- Test gauge serial
- G-3784
- Gauge calibration date
- May 26, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-24-01274
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.