Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8879 Orchard Dr

Approved

Filed Oct 12, 2024 by Reese Nguyen, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Oct 12, 2024
Assembly type
RP
Serial number
K478423
Size
1
Test gauge serial
G-3378
Gauge calibration date
Jan 21, 2024
Check valve 1
3.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-11-01135
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8879 Orchard Dr
Owner: Casey Brandt
Parcel 107-11-01135