Routt County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Dental

Approved

Filed Dec 1, 2023 by Alex Pruitt, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Dec 1, 2023
Assembly type
DC
Serial number
A953259
Size
2
Test gauge serial
G-3217
Gauge calibration date
Aug 16, 2022
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-30-01162
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6950 Fox Run Ln
Owner: Hollins Holdings LLC
Parcel 107-30-01162