Backflow assembly test · 7042 Mill Creek Way
ApprovedFiled Mar 29, 2025 by Avery Fairley, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 29, 2025
- Assembly type
- PVB
- Serial number
- Z816513
- Size
- 3/4
- Test gauge serial
- G-3040
- Gauge calibration date
- Jun 25, 2024
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-91-01349
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7042 Mill Creek Way
Owner: Riley Harlow
Parcel 117-91-01349