← Backflow review queue
Backflow assembly test · 5465 Sycamore Rd
ApprovedFiled Nov 27, 2024 by Avery Fairley, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 27, 2024
- Assembly type
- DC
- Serial number
- K336979
- Size
- 3/4
- Test gauge serial
- G-4895
- Gauge calibration date
- Oct 11, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-71-01165
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5465 Sycamore Rd
Owner: Drew Ashby
Parcel 117-71-01165