← Backflow review queue
Backflow assembly test · 3765 Orchard Dr
ApprovedFiled May 31, 2025 by Avery Fairley, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- May 31, 2025
- Assembly type
- RP
- Serial number
- A959908
- Size
- 3/4
- Test gauge serial
- G-3216
- Gauge calibration date
- Aug 13, 2024
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-41-01344
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.