← Backflow review queue
Backflow assembly test · 7442 Spring Branch Rd
ApprovedFiled Aug 21, 2024 by Avery Fairley, Summit Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Aug 21, 2024
- Assembly type
- PVB
- Serial number
- Z743684
- Size
- 1
- Test gauge serial
- G-3255
- Gauge calibration date
- Mar 10, 2024
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 117-82-01004
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7442 Spring Branch Rd
Owner: Alex Whitcomb
Parcel 117-82-01004