Weld County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2549 Orchard Way

Approved

Filed Aug 23, 2024 by Blake Hollins, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Aug 23, 2024
Assembly type
RP
Serial number
B471783
Size
3/4
Test gauge serial
G-2256
Gauge calibration date
Feb 24, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 123-37-01058
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2549 Orchard Way
Owner: Quinn Calloway
Parcel 123-37-01058