Weld County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Station Bakery

Approved

Filed May 24, 2026 by Drew Wexler, Lakeside Plumbing & Backflow · filed from phone

Report

Date of service
May 24, 2026
Assembly type
RP
Serial number
W237434
Size
1
Test gauge serial
G-8177
Gauge calibration date
Oct 30, 2025
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 123-78-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2951 Turkey Hill Ct
Owner: Ashby Holdings LLC
Parcel 123-78-01294