← Backflow review queue
Backflow assembly test · 2044 Old Church Ln
ApprovedFiled Jun 23, 2025 by Casey Fairley, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jun 23, 2025
- Assembly type
- RP
- Serial number
- K781795
- Size
- 3/4
- Test gauge serial
- G-8001
- Gauge calibration date
- Feb 6, 2025
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-60-01091
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2044 Old Church Ln
Owner: Morgan Danner
Parcel 001-60-01091