Backflow assembly test · 604 Stone Gate Dr

Approved

Filed Dec 17, 2025 by Alex Okafor, Keystone Backflow Testing · filed from phone

Report

Date of service
Dec 17, 2025
Assembly type
PVB
Serial number
K185450
Size
3/4
Test gauge serial
G-4508
Gauge calibration date
May 10, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-64-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.