Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6242 Hickory Ln

Approved

Filed Oct 23, 2024 by Casey Fairley, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Oct 23, 2024
Assembly type
RP
Serial number
A180557
Size
1
Test gauge serial
G-7899
Gauge calibration date
Jul 15, 2024
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-19-01321
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6242 Hickory Ln
Owner: Jordan Ashby
Parcel 001-19-01321