Backflow assembly test · 6258 Mill Creek Trl

Approved

Filed Mar 9, 2025 by Casey Fairley, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Mar 9, 2025
Assembly type
DC
Serial number
K173855
Size
1
Test gauge serial
G-6302
Gauge calibration date
Oct 17, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-97-01146
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.