Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 548 Spring Branch Ln

Approved

Filed Jun 25, 2026 by Alex Okafor, Keystone Backflow Testing · filed from phone

Report

Date of service
Jun 25, 2026
Assembly type
RP
Serial number
Z285300
Size
1
Test gauge serial
G-8260
Gauge calibration date
Apr 6, 2026
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-55-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

548 Spring Branch Ln
Owner: Riley Benton
Parcel 001-55-01256