Kent County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6039 Cedar Hollow Rd

Approved

Filed Dec 2, 2025 by Avery Hollins, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Dec 2, 2025
Assembly type
DC
Serial number
K275915
Size
3/4
Test gauge serial
G-4617
Gauge calibration date
Jan 5, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-74-01357
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6039 Cedar Hollow Rd
Owner: Jamie Ellery
Parcel 001-74-01357