Backflow assembly test · Maple Leaf Bakery
ApprovedFiled Apr 27, 2025 by Alex Okafor, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Apr 27, 2025
- Assembly type
- DC
- Serial number
- K418685
- Size
- 1
- Test gauge serial
- G-6599
- Gauge calibration date
- Nov 1, 2024
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-88-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3479 Stone Gate Ln
Owner: Ellery Holdings LLC
Parcel 001-88-01297