New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8304 Old Church Ln

Approved

Filed Jul 8, 2024 by Logan Nguyen, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Jul 8, 2024
Assembly type
DC
Serial number
A119039
Size
1
Test gauge serial
G-6676
Gauge calibration date
Oct 30, 2023
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-55-01229
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8304 Old Church Ln
Owner: Jamie Wexler
Parcel 003-55-01229