New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Diner

Filed Nov 22, 2026 by Reese Vance, Valley Backflow Testing · filed from phone

Report

Date of service
Nov 22, 2026
Assembly type
RP
Serial number
A617155
Size
4
Test gauge serial
G-7908
Gauge calibration date
Apr 29, 2026
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
1.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-80-01076
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Property

3418 Stone Gate Ln
Owner: Ramirez Holdings LLC
Parcel 003-80-01076