New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8433 Cedar Hollow Trl

Approved

Filed Oct 3, 2025 by Reese Vance, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Oct 3, 2025
Assembly type
RP
Serial number
B355554
Size
3/4
Test gauge serial
G-3130
Gauge calibration date
Apr 28, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-84-01273
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8433 Cedar Hollow Trl
Owner: Quinn Lindqvist
Parcel 003-84-01273