Backflow assembly test · 8406 Cedar Hollow Ct
ApprovedFiled Feb 1, 2024 by Blake Harlow, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Feb 1, 2024
- Assembly type
- PVB
- Serial number
- W921899
- Size
- 3/4
- Test gauge serial
- G-8410
- Gauge calibration date
- Sep 19, 2023
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-27-01202
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.