Backflow assembly test · Two Rivers Car Wash

Approved

Filed Feb 7, 2025 by Logan Nguyen, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Feb 7, 2025
Assembly type
DC
Serial number
Z850504
Size
2
Test gauge serial
G-5825
Gauge calibration date
Aug 27, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-16-01270
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.