Backflow assembly test · Two Rivers Car Wash
ApprovedFiled Feb 7, 2025 by Logan Nguyen, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 7, 2025
- Assembly type
- DC
- Serial number
- Z850504
- Size
- 2
- Test gauge serial
- G-5825
- Gauge calibration date
- Aug 27, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 003-16-01270
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.