New Castle County, DECompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Hilltop Medical Offices

Approved

Filed Apr 9, 2025 by Logan Nguyen, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Apr 9, 2025
Assembly type
RP
Serial number
A306875
Size
1
Test gauge serial
G-7464
Gauge calibration date
Nov 27, 2024
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 003-26-01124
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3348 Pine Knoll Dr
Owner: Fairley Holdings LLC
Parcel 003-26-01124